Technical Specifications
- Product Code : HFN020
- Series : HFN Series (Aluminium Profile 150 mm)
- Filtration Class : H13 (Efficiency ≥99.95% @ 0.3 μm / MPPS, EN 1822)
- Dimensions : 610 x 915 x 150 mm (24 x 36 x 6 inches)
- Media Area : 15.6 m²
- Airflow Capacity : 900 m³/h
- Filter Media : High-quality Microglass Fiber
- Frame : Extruded Anodized Aluminium
- Separator : Hotmelt
- Gasket : Half Round Endless Polyurethane (Up Stream)
- Protection Grids : Painted Aluminium on both sides
- Final Pressure Drop : 600 Pa
- Maximum Operating Temperature : 80°C
- Dimensional Tolerance : Safe up to ±10 mm difference with housing
Key Advantages
- High H13 efficiency – captures ≥99.95% of particles at 0.3 microns
- Deep 150 mm pleat with 15.6 m² media area – outstanding dust-holding capacity and extended service life
- High airflow capacity 900 m³/h – suitable for large AHU/FFU systems
- Upstream endless polyurethane gasket – reliable, leak-free sealing
- Anodized aluminium frame – lightweight, corrosion-resistant, and durable
- Dual-sided painted aluminium grids – maximum media protection
- ±10 mm tolerance – flexible fit in various housings
Applications
- Air conditioning systems in hospitals, operating theaters, isolation rooms, laboratories, museums
- Industrial processes in pharmaceutical plants, food & beverage, microelectronics
- Large cleanrooms, high-volume ventilation, and sensitive production facilities
The HEPA Filter H13 MIKROPOR HFN020 provides superior air filtration with ≥99.95% efficiency at 0.3 microns (EN 1822 certified). It effectively removes ultra-fine dust, bacteria, viruses, pollen, and microscopic contaminants. With dimensions 610 x 915 x 150 mm, 15.6 m² media area, and 900 m³/h airflow capacity, this deep-pleat model is engineered for high-volume systems requiring maximum air purity, such as large cleanrooms, hospital operating suites, pharmaceutical facilities, and microelectronics production. The 150 mm depth significantly increases dust-holding capacity and service life compared to standard models.
Equipped with premium microglass fiber media, anodized aluminium frame, upstream endless polyurethane gasket, and dual-sided protection grids, the HFN020 delivers stable performance, perfect sealing, and long-term reliability in critical environments.
Filtration Stage Sequence
- Pre-filter (G4) – removes large dust and coarse particles
- Medium/Fine filter (F7–F9) – captures medium to fine particles
- HEPA H13 – final stage for maximum cleanliness
Installation Instructions
- Ensure housing/plenum is clean before installation.
- Check knife-edge or sealing surface for cleanliness and damage.
- Remove old filter carefully (use PPE).
- Install new filter: align upstream gasket side, lower gently until fully seated.
- Confirm level and proper alignment.
- Perform DOP/PAO leak test after installation.
When to Replace the HEPA Filter
- Final pressure drop reaches or exceeds 600 Pa
- Significant rise in differential pressure → higher fan load and energy use
- Leak test fails (mandatory every 6–12 months per ISO/GMP)
- Typical service life 1–3 years (depending on dust load and pre-filter quality)